|
PHASE |
Single phase with ground |
|
CAPACITY |
2000 VA / 1800 W |
|
INPUT |
|
|
Nominal Voltage |
100/110/115/120/127VAC or 200/208/220/230/240VAC |
|
Voltage Range Low Line Transfer |
60 VAC / 70 VAC / 80 VAC / 90 VAC ± 5 % or 120 VAC / 140 VAC / 160 VAC / 180 VAC ± 5 % |
|
|
( based on load percentage0% - 60 % / 60 % - 70 % / 70 - 80 % / 80 % - 100%) |
|
Low Line Comeback |
70 VAC / 80 VAC / 90 VAC / 100 VAC ± 5 % or 135 VAC / 155 VAC / 175 VAC / 195 VAC ± 5 % |
|
|
( based on load percentage 0% - 60 % / 60 % - 70 % / 70 - 80 % / 80 % - 100%) |
|
High Line Transfer |
140VAC / 150 VAC ± 5 % or 280 VAC / 300 VAC ± 5 % |
|
|
( based on load percentage0 - 80 % / 80 % - 100%) |
|
High Line Comeback |
135VAC / 140 VAC ± 5 % or 270VAC / 280 VAC ± 5 % |
|
|
( based on load percentage0 - 80 % / 80 % - 100%) |
|
Frequency Range |
40Hz ~ 70 Hz |
|
Power Factor |
>= 0.99 @ Nominal Voltage (100% load) |
|
OUTPUT |
|
|
Output Voltage |
100/110/115/120/127VAC or 200/208/220/230/240VAC |
|
Voltage Regulation |
± 1% |
|
Frequency Range (Synchronized Range) |
47~ 53 Hz or 57 ~ 63 Hz |
|
Frequency Range (Batt. Mode) |
50 Hz or 60Hz ± 0.5% |
|
Current Crest Ratio |
3:1 |
|
Harmonic Distortion |
<= 3 % THD (Linear Load) |
|
|
<= 6 % THD (Non-linear Load) |
|
Transfer Time AC to DC |
Zero |
|
Inverter to Bypass |
4 ms (Typical) |
|
Waveform (Batt. Mode) |
Pure Sinewave |
|
EFFICIENCY |
|
|
To AC Mode |
89,00% |
|
To Battery Mode |
85,00% |
|
BATTERY |
|
|
Standard Model Battery Type |
12 V / 9 AH |
|
Typical Recharge Time |
4 hours recover to 90% capacity |
|
Charging Current (max.) |
1.0 A |
|
Charging Voltage |
54.7 VDC ±1% |
|
INDICATORS |
|
|
LCD |
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
|
ALARM |
|
|
Battery Mode |
Sounding every 4 seconds |
|
Low Battery |
Sounding every second |
|
Overload |
Sounding twice every second |
|
Fault |
Continuously sounding |
|
PHYSICAL |
|
|
Standard Model Dimension, D x W x H |
397 x 145 x 220 |
|
(mm) |
|
|
Net Weight (kgs) |
17 |
|
ENVIRONMENT |
|
|
Humidity |
20-90 % RH @ 0- 40В°C (non-condensing) |
|
Noise Level |
Less than 50dBA @ 1 Meter |
|
MANAGEMENT |
|
|
Optional SNMP |
Power management from SNMP manager and web browser |
|
Smart RS-232/USB |
Supports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC according software list |
|
Standard |
CE,EN62040-1,EN62040-2 |